Caracteristici tehnice MCCBs - fixed version Thermal adjustable from 0.8 to 1 In Magnetic fixed at 10 In (fixed at 400 A for In from 16 A to 40 A) Breaking capacity Icu 100 kA (400 V~) 4P In : 16 A Caracteristici generale DPX³ 125 HP - thermal magnetic release MCCBs from 16 to 125 A - fixing on plate Moulded case MCCBs for switching, control isolation and protection of low Tensiune electrical lines Can be fitted with auxiliaries Furnizat cu: screws for connections, fixing screws and insulated shields (phase barriers) Can be fitted with cage terminals 120 mm² max. (flexible cable) or 150 mm² max. rigid cable Conform to IEC 60947-2 Sealable adjustment Can be mounted on plate in XL³ and XL³ S cabinets and enclosures